TriStar PWM

Objects and Definitions

Data

This is the complete list of data objects that can be accessed using the Data dropdown on the dashboard

Object Description Type Symbol
adc_vb_f Battery voltage, filtered (τ ≈ 1s) volts V
adc_vs_f Battery sense voltage, filtered (τ ≈ 2.5s) volts V
adc_vx_f Load voltage, filtered (τ ≈ 2.5s) volts V
adc_ipv_f Charging current, filtered (τ ≈ 2.5s) amps A
adc_iload_f Load current, filtered (τ ≈ 2.5s) amps A
Vb_f Battery voltage, slow filter (τ ≈ 25s) volts V
T_hs Heatsink temperature celsius °C
T_batt Battery temperature (RTS connected) (0x80 if not connected) celsius °C
V_ref Charge regulator reference voltage volts V
Ah_r Ah resetable amp-hours Ah
Ah_t Ah total amp-hours Ah
hourmeter Hourmeter hours h
alarm Alarm Bitfield array
fault Fault Bitfield array
dip_switch Dip Switch Settings at Power On (switch[1..8] in bits[0..7]) array
control_mode Control mode string
control_state Control state string
d_filt PWM duty cycle integer
EV_reg Regulation Voltage @ 25ºC volts V
EV_float Float Voltage @ 25ºC volts V
Et_float Time Before Entering Float seconds s
Et_floatlb Time Before Entering Float due to Low Battery seconds s
EV_floatlb_trip Voltage Trigger for Low Battery Float Time volts V
EV_float_cancel Voltage to cancel float volts V
EV_eq Equalize Voltage @ 25ºC volts V
Et_eqcalendar Days Between EQ Cycles days d
Et_eq_above Equalize Time Limit above EV_reg seconds s
Et_eq_reg Equalize Time Limit at EV_eq seconds s
EV_tempcomp Temperature Compensation Coefficient volts V
EV_hvd High Voltage Disconnect @ 25ºC volts V
EV_hvr High Voltage Reconnect volts V
Etmr_eqcalendar Days since last equalize days d
Et_float_exit_cum Cum. time at 100% duty cycle, exit float seconds s
Ed_float_enter Duty Cycle to begin Float transition counter percentage %
Eb_diversion_pwm Diversion regulation type (PWM or On-Off) string
EV_lvd Low Voltage Disconnect volts V
EV_lvr Low Voltage Reconnect volts V
EV_lhvd Load High Voltage Disconnect volts V
EV_lhvr Load High Voltage Reconnect volts V
ER_icomp LVD Load Current Compensation ohms Ω
Et_lvd_warn LVD Warning Timeout seconds s
Et_sun1 Lighting Time after sunset seconds s
Et_sun2 Lighting Time before sunrise seconds s
Eb_light_config Lighting Configuration Bits array
EV_night_max Night time threshold – Array Voc volts V
EV_day_min Morning threshold for timing – Array Voc volts V
EV_relaxed_day Morning threshold for lighting – Array Voc volts V
EV_soc_g_gy LED Green to Green&Yellow Limit volts V
EV_soc_gy_y LED Green&Yellow to Yellow Limit volts V
EV_soc_y_yr LED Yellow to Yellow&Red Limit volts V
EV_soc_yr_r LED Yellow&Red to Red Flashing Limit volts V
ETb_max Max Battery Temp Compensation Limit celsius °C
ETb_min Min Battery Temp Compensation Limit celsius °C
Emb_tristar_id Modbus TriStar server ID integer
Et_batt_service days between battery service intervals days d
Etmr_batt_service days since last battery service days d
Ehourmeter Hourmeter hours h
EAhl_r Ah Load Resettable amp-hours Ah
EAhl_t Ah Load Total amp-hours Ah
EkWh Kilowatt hours kilowatt-hours kWh
EVb_min Battery Voltage Minimum volts V
EVb_max Battery Voltage Maximum volts V
Emb_meterbus_id Meterbus ID integer

Action

Object Description
eq Trigger equalize charge
disconnect_on Control disconnect on
disconnect_off Control disconnect off
Ah_r Reset Ah resettable
Ah_t Reset Ah total
kWh_r Reset kWh resettable
reset_service Reset batt service reminder
clear_faults Clear faults
clear_alarms Clear alarms
EEPROM Reset EEPROM
lvd_override LVD override for one cycle
reset Reset controller

2 Hour Logs

These objects are logged every 2 hours.

Objects:

  • adc_vb_f
  • adc_vx_f
  • adc_ipv_f
  • adc_iload_f
  • T_hs
  • control_state

Daily Logs

These objects are logged once every day.

Objects:

Alerts

These objects are scanned every few seconds and alerts will be sent as soon as any critical issues are detected.

Objects:

  • control_state
  • fault
  • alarm